Tl latest moto-control specific digital signal processors (DSP) with clock frequency reaching up to 150Hz are adopted.
Asynchronous motors and permanent magnet synchronous motors control are supported, with accurate autotuning.Two independent motor profiles are programmed, and the switch over of the two motors control can be realized by parameter setting or terminal input.
ln V/Fcontrol mode accurate current limited control function makes sure of no over-curmernt fault occurred no matter the drives are running at acceleration/deceleration, or rotor locked status, well protecting the drves. h vector control mode, acurate torque limited control pledges powerful or moderate torque complying with application requirements , protecting machinery well.
In V/F separated control mode,output frequency and cutput voltage can be set respectively ft for applications,such as variable frequency power sources , torque motors, etc.
Control mode |
Starting torque |
Speed range |
Speed accur acy |
Torque response |
V/F control |
0.5Hz180% |
1:100 |
±0.5% |
|
Speed-sensorless control 1 |
0.5Hz 180% |
1:100 |
±0.2% |
<10ms |
Speed-sensorless control 2 |
0.25Hz 180% |
1:200 |
±0.2% |
<10ms |
Speed-senso control |
OHz200% |
1:1000 |
±0.02% |
<5ms |
Rated input voltage | Rated input current | Frequency | Allowable voltage range |
3-phase 380VAC/400VAC/415VAC 440VAC/460VAC/480VAC |
SEE the table “Modeland technical parameters of SCK300 series' |
50HZ/60Hz,tolerarce ±5% |
Voltage consecutive fluctuation ±10%,short fluctuation-15%~10% ie.323V~528V Voltage out-of-balance rate:<3%,THD meets the standards of IEC61800-2 |
Applicable motor | Rated current | Output voltage | Output frequency | Over load capability |
See the table "Model and technical parameters of SCK300ceriau.F |
See the table "Model andtechnical parametersof SCK300 series" |
3-phase:0-rated input voltage, error less than±3% | 0.00HZ-600Hz Resolution 0.01HZ |
150% 1min: 180% 10s;200% 0.5s. once per 10min. |
Contol pattern |
V/F control |
Speed-sensor |
Soeed-sensor |
Speed-sensor control |
Starting torque |
0.5Hz180% |
0.5Hz180% |
0.25H180% |
0Hz 200% |
Speed range |
1:100 |
1:100 |
1:200 |
1:100 |
Speed accuracy |
±0.5% |
±0.2% |
±0.2% |
±0.02% |
Speed ripple |
- |
±0.3% |
±0.3% |
±0.1% |
Torque control |
NO |
NO |
Yes |
yes |
Torque accuracy |
- |
- |
±7.5% |
±5% |
Torque response |
- |
<10ms |
<10ms |
<.5ms |
Positioning |
- |
- |
- |
±1Line pulse±1 |
Start frequency | 0.00Hz-600.00Hz |
Accel/Decel time | 0.00s-3600s |
Carrier fequency | 1.0KHz~ 15.0KHz |
Freguency command mod | Digital setting +Keypad Up/Down: Digital setting+terminal Up/Down.Communication setting. Analogsetting: All/AI2/AB.Terminal pulse setting. |
start methods | Start from starting frequency. DC injection braking at start; Flying start. |
Stop methods | Ramp to stop. Coast to stop. DC injection braking at ramp stop. |
Dynamic brake capability | Braking unit triggered voltage:650-750V. Service time:0.0-100.0s. Brake units of SCK300G3-037and below areopti onally inbuilt. |
DC braking capability | DC braking start frequency:0.00-600.00Hz. DC braking current: constart torque 0.0~100%.DC braking time:0.0-100s. |
Input terminals | Eight switching input terminals, one high speed pulse input terminal. Support dry node, active PIP, NP input mode;Two analog input terminals, one of which can only be used as a voltage input and the other is optional. |
output terminals | One high-speed pulse output(0-50kHZ square wave output and two analog outputs (voltage/current programmable)can output signals such as command frequency, output frequency, etc one digital output.Two relay outputs. |
Ercode input terminal | Support 5V/ 12V voltage grade. Support OC push-pull. differential signal inputsand such. |
Field |
Altitude |
Temperature |
Humidity |
Vibration |
Storage |
In doors,no direct sunlight, |
0m-2000m:de-rate |
-10C-+40℃ |
5%-95% |
Less thar |
-40℃-+70℃ |
Category | Analog input | |
Terminal |
Terminal designation |
Specification |
+10V | Analog input reference voltage |
Voltage:10.3V±3% Maximum output current: 25mA.ad resistance of external potentiometer should be larger than 4000 |
GND | Analog ground | Isolated from COM interior ly |
AI2 | Ana log input 2 | The voltage and current can be 0-10V/0-20mA, which can be switched by route switch J4. Input impedance: voltage input is 20kΩ, current input is 500kQ Resolution: When 10V corresponds to 50Hz, the minimum resolution is 5mV Error ±1%,25°C |
A13 | Ana log input 3 | -10V~10V voltage Input impedance: 20kO at voltage input Resolution: When 10V corresponds to 50Hz. the minimum resolution is 5mV Error ±1%,25°C |
Category | Analog input | |
Terminal |
Terminal designation |
Specification |
AO1 | Analog output 1 | 0mA-20mA; impedance200-500Ω.0-10V:impedance>10kΩ2. 0mA-20mA; input impedance 500Q, maximum input current 25mA. Switch J1 on control board for jumping between0~20mAand0~10V.Factory default:0-10V. |
AO2 | Analog output 2 | 0mA ~20mA:impedance200~500Ω.0~10V:impedance>10kΩ. 0mA-20mA;input impedance 50002.maximum input current 25mA. Switch J2 on control board for jumping between0-20mA and 0-10V. Factory default 0-10V. |
CND | Analog ground | lsolated from COM Interior ly |
Category |
Terminal |
Terminal designation |
Specification |
|
Digital |
DO1 |
open collector autput | voltage range:0-24V | Current range:0-50mA |
HDO |
open collector out/Pulse out | Open collector output: same as DO1 | Pulse output:0~50KHz | |
Relay output | RO1A/RO1B/RO1C RO2A/RO2B/RO2C |
Two sets of relay outputs | RO1A common end. RO1B normally closed. RO1C normally open RO2A common end. RO2B normally closed.RO2C is always on |
Contact capacity: 250VAG3A.30VDC1A. |
Category | Analog input | |
Terminal |
Terminal designation |
Specification |
+24V | +24V | 24V±10%,isolated from GFNID inter iorly Maximun load 200mA |
PLC | Digital input common terminal | Switch between high level and low level.Short-circuited with ±24V at delivery. low value of digital irput valid, external power input. |
COM | +24V ground | Isolated from GNID interiorly |
S1-S8 | Digital input terminals1-8 | Input:24VDC.5mA Frequency range:0-200Hz Voltage range:10-30V |
HDI | Digital input/Pulse input | Voltage range:10-30V Digital input: same as S1-S8 Pulse input:0.1~50kHz; |
Cate gory | Terminal 485 interface | Keypad 485 interface |
Terminal |
Terminal designation |
Specification |
485+ | Differential signal 485+ |
Rate: 1200/2400/4800/9600/19200/38400/57600bps |
485- | Differential signal 485- | |
GND | 485communication shielded ground | lsolated from COM inter iorly |
Model |
SCK300 series appearance and installation dimensions (mm) |
||||||
W | WI | H | H1 | D | D1 | Φ | |
SCK300 G3-0D75 |
108 |
96 |
134 |
118 |
149 |
140 |
5 |
SCK300 G3-1D5 | |||||||
SCK300 G3-2D2 | |||||||
SCK300G3-004 | |||||||
SCK300 G3-5D5/P3-7D5 |
180 |
167 |
240 |
228 |
214 |
205 |
5.5 |
SCK300G3-7D5/P3-011 | |||||||
SCK300 G3-011/P3-015 | |||||||
SCK300G3-015/P3-018 |
225 |
200 |
354 |
330 |
211 |
205 |
6 |
SCK300G3-018/P3-022 | |||||||
SCK300G3-022/P3-030 | |||||||
SCK300G3-030/P3-037 |
240 |
165 |
450 |
433 |
236 |
230 |
7 |
SCK300 G3-037/P3-045 | |||||||
SCK300 G3-045/P3-055 |
240 |
160 |
560 |
545 |
331 |
321 |
7 |
SCK300 G3-055/P3-075 | |||||||
SCK300G3-075/P3-090 |
270 |
195 |
640 |
617 |
378 |
368 |
10 |
SCK300G3-090/P3-110 | |||||||
SCK300 G3-110/P3-132 | |||||||
SCK300G3-132/P3-160 |
352 |
220 |
800 |
777 |
418 |
408 |
10 |
SCK300 G3-160/P3-185 | |||||||
SCK300G3-185/P3-200 |
360 |
200 |
940 |
912 |
494.5 |
484.5 |
17.5 |
SCK300G3-200/P3-220 | |||||||
SCK300G3-220/P3-250 | |||||||
SCK300G3-250/P3-280 |
370 |
200 |
1140 |
1112 |
575.5 |
565.5 |
17.5 |
SCK300G3-280/P3-315 | |||||||
SCK300 G3-315/P3-350 |
400 |
240 |
1250 |
1222 |
560 |
550 |
17.5 |
SCK300G3-350/P3-400 | |||||||
SCK300 G3-400/P3-450 |
Note: the above dimensions are subject to change without prior notice.